Does an open-plan ground floor affect fire safety? Removing the hallway wall explained

The short answerIt can. Building regulations treat means of escape as a requirement a wall removal must not make worse. In most two-storey houses an open-plan ground floor works if upstairs rooms have escape windows. In a house with a floor more than 4.5m above ground, such as after a loft conversion, the stair needs protecting, so open plan needs extra measures.

Why is fire safety part of a wall removal?

Because of how the Building Regulations define a material alteration. Regulation 3 of the Building Regulations 2010 lists means of warning and escape (paragraph B1) as a relevant requirement, alongside Part A for structure. An alteration that would leave the house less compliant on escape counts as building work, even if the beam is perfect.

The hallway wall is the one that matters most, because it often encloses the stair.

What does Approved Document B say for a two-storey house?

Approved Document B, Volume 1 covers dwellings. For the ground floor, it says habitable rooms other than kitchens should either open onto a hall leading to a final exit, or have an emergency escape window or door.

For upper storeys no more than 4.5m above ground with one stair, each habitable room other than a kitchen should have an emergency escape window or external door, or direct access to a protected stairway.

So can I open the stairs into the living room?

In a typical two-storey house, often yes, provided the bedrooms have suitable escape windows. Then the upstairs does not rely on a protected stair, and the ground-floor rooms rely on their own escape windows or doors.

Check the windows before you design the layout. Building control will look at the escape route as well as the steel.

What changes in a three-storey house or after a loft conversion?

Once a house has a storey more than 4.5m above ground, Approved Document B expects a protected stairway: a stair separated by fire-resisting construction (minimum REI 30) at all storeys, leading to a final exit, or an alternative escape route from the top storey.

For a loft conversion it says that where the layout is open plan, new partitions should enclose the escape route.

Is there an alternative to keeping the hallway wall?

For a loft conversion over an open-plan ground floor, Approved Document B describes an alternative where all of these are provided:

  • Sprinkler protection to the open-plan areas
  • A fire-resisting partition (minimum REI 30) and door (minimum E 20) separating the ground storey from the upper storeys, with the loft occupants able to reach a first-floor escape window
  • Cooking facilities separated from the open-plan area by fire-resisting construction (minimum REI 30)

Does the steel beam itself need fire protection?

Usually, yes. A beam carrying the floor above is part of the structure that has to stand up in a fire long enough for people to get out. It is normally boxed in fire-rated plasterboard or painted with an intumescent coating, and building control check it before signing off.

What should I sort out before work starts?

Tell the engineer and building control about the whole layout, not just the wall. If a loft conversion is planned later, design for it now, because the escape route is easier to get right before the kitchen goes in. A full plans application suits this kind of job, because the layout is checked before work begins.

Related questions

Do I need a fire door to the kitchen in an open-plan house?

In a two-storey house, not usually, since Approved Document B allows a kitchen as an inner room. With a storey above 4.5m, the kitchen may need separating as part of the alternative approach. Building control will confirm for your layout.

What counts as an emergency escape window?

A window big enough and low enough to climb out of, meeting the sizes in Approved Document B. Many older windows do not, so check before relying on them.

Are smoke alarms required?

Means of warning is part of the same B1 requirement. Approved Document B expects mains-operated smoke alarms with a standby power supply, in the circulation spaces where an alteration calls for them. Ask building control what your layout needs.